National Pollutant Discharge Elimination System (NPDES) Permit Program FACT SHEET Regarding an NPDES Permit To Discharge to Waters of the State of Ohio for Duke Energy Ohio, Inc. Walter C. Beckjord Station Public Notice No.: 13-10-009 Public Notice Date: October 2, 2013 Comment Period Ends: November 1, 2013 Ohio EPA Permit No.: 1IB00000*MD Application No.: OH0009865 Name and Address of Applicant: Duke Energy Ohio, Inc. Walter C. Beckjord Station 139 East Fourth Street, Room EM740 Cincinnati, Ohio 45202 Name and Address of Facility Where Discharge Occurs: Duke Energy Ohio, Inc. Walter C. Beckjord Station 757 State Route 52 New Richmond, Ohio 45157 Clermont County Receiving Water: Pond Run Creek Tenmile Creek, Ohio River Subsequent Stream Network: Ohio River Introduction Development of a Fact Sheet for NPDES permits is mandated by Title 40 of the Code of Federal Regulations (CFR), Section 124.8 and 124.56. This document fulfills the requirements established in those regulations by providing the information necessary to inform the public of actions proposed by the Ohio Environmental Protection Agency (Ohio EPA), as well as the methods by which the public can participate in the process of finalizing those actions. This Fact Sheet is prepared in order to document the technical basis and risk management decisions that are considered in the determination of water quality based NPDES Permit effluent limitations. The technical basis for the Fact Sheet may consist of evaluations of promulgated effluent guidelines, existing effluent quality, instream biological, chemical and physical conditions, and the relative risk of alternative effluent limitations. This Fact Sheet details the discretionary decision-making process empowered to the Director by the Clean Water Act (CWA) and Ohio Water Pollution Control Law (Ohio Revised Code [ORC] 6111). Decisions to award variances to Water Quality Standards (WQS) or promulgated effluent guidelines for economic or technological reasons will also be justified in the Fact Sheet where necessary. Effluent limits based on available treatment technologies are required by Section 301(b) of the Clean Water Act. Many of these have already been established by the United States EPA (U.S. EPA) in the effluent guideline regulations (a.k.a. categorical regulations) for industry categories in 40 CFR Parts 405-499. Technology-based regulations for publicly-owned treatment works are listed in the Secondary Treatment Regulations (40 CFR Part 133). If regulations have not been established for a category of dischargers, the director may establish technology-based limits based on best professional judgment (BPJ). Ohio EPA reviews the need for water-quality-based limits on a pollutant-by-pollutant basis. Wasteload allocations (WLAs) are used to develop these limits based on the pollutants that have been detected in the discharge, and the receiving water’s assimilative capacity. The assimilative capacity depends on the flow in the water receiving the discharge, and the concentration of the pollutant upstream. The greater the upstream flow, and the lower the upstream concentration, the greater the assimilative capacity is. Assimilative capacity may Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -1- represent dilution (as in allocations for metals), or it may also incorporate the break-down of pollutants in the receiving water (as in allocations for oxygen-demanding materials). The need for water-quality-based limits is determined by comparing the WLA for a pollutant to a measure of the effluent quality. The measure of effluent quality is called Projected Effluent Quality (PEQ). This is a statistical measure of the average and maximum effluent values for a pollutant. As with any statistical method, the more data that exists for a given pollutant, the more likely that PEQ will match the actual observed data. If there is a small data set for a given pollutant, the highest measured value is multiplied by a statistical factor to obtain a PEQ; for example if only one sample exists, the factor is 6.2, for two samples - 3.8, for three samples - 3.0. The factors continue to decline as samples sizes increase. These factors are intended to account for effluent variability, but if the pollutant concentrations are fairly constant, these factors may make PEQ appear larger than it would be shown to be if more sample results existed. Summary of Permit Conditions The effluent limits and monitoring requirements in this permit are mostly the same as the previous permit. New copper limits are proposed at Outfalls 002 and 005 based on the reasonable potential to exceed WQS. New E. coli limits are proposed at Outfall 005 in accordance with new WQS. New monitoring for arsenic, barium, and zinc is proposed at Outfall 025 based on the reasonable potential to exceed WQS. The limit for zinc is proposed to be removed at Outfall 009. Monitoring for strontium is proposed to be removed at Outfall 012. Monitoring for boron is proposed to be removed at Outfall 025. None of these parameters have the reasonable potential to exceed WQS. In Part II of the permit, special conditions are included that operator certification, minimum staffing and operator of record; outfall signage; and thermal loading calculations. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -2- Table of Contents Page Introduction ................................................................................................................................................... 1  Summary of Permit Conditions ..................................................................................................................... 2  Procedures for Participation in the Formulation of Final Determinations .................................................... 5  Location of Discharge/Receiving Water Use Classification ......................................................................... 6  Facility Description ....................................................................................................................................... 6  Description of Existing Discharge ................................................................................................................ 6  Assessment of Impact on Receiving Waters ................................................................................................. 9  Development of Water-Quality-Based Effluent Limits ................................................................................ 9  Reasonable Potential/ Effluent Limits/Hazard Management Decisions ..................................................... 11  Other Requirements .................................................................................................................................... 17  List of Figures Figure 1. Approximate Location of Duke Energy Inc., Beckjord Station .................................................. 19 Figure 2. Approximate Location of Beckjord Outfalls .............................................................................. 20 List of Tables Table 1. Effluent Characterization Using NPDES Application Form 2C .................................................. 21 Table 2. Effluent Characterization Using Ohio EPA Data ......................................................................... 30 Table 3. Effluent Characterization Using Self-Monitoring Data ............................................................... 31 Table 4. Projected Effluent Quality for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025................... 34 Table 5. Ohio EPA Bioassay Acute Toxicity Results ................................................................................ 37 Table 6. Water Quality Criteria in the Study Area ..................................................................................... 38 Table 7. Instream Conditions and Discharger Flow ................................................................................... 39 Table 8. Summary of Effluent Limits to Maintain Applicable Water Quality Criteria ............................. 42 Table 9. Parameter Assessment for Outfalls 002, 003, 005, 009, 012, 023, and 025................................. 43 Table 10. Final Effluent Limits for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 ......................... 50 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -3- List of Attachments Attachment 1. Applicable Federal Effluent Guidelines ............................................................................. 53 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -4- Procedures for Participation in the Formulation of Final Determinations The draft action shall be issued as a final action unless the Director revises the draft after consideration of the record of a public meeting or written comments, or upon disapproval by the Administrator of the U.S. Environmental Protection Agency. Within thirty days of the date of the Public Notice, any person may request or petition for a public meeting for presentation of evidence, statements or opinions. The purpose of the public meeting is to obtain additional evidence. Statements concerning the issues raised by the party requesting the meeting are invited. Evidence may be presented by the applicant, the state, and other parties, and following presentation of such evidence other interested persons may present testimony of facts or statements of opinion. Requests for public meetings shall be in writing and shall state the action of the Director objected to, the questions to be considered, and the reasons the action is contested. Such requests should be addressed to: Legal Records Section Ohio Environmental Protection Agency P.O. Box 1049 Columbus, Ohio 43216-1049 Interested persons are invited to submit written comments upon the discharge permit. Comments should be submitted in person or by mail no later than 30 days after the date of this Public Notice. Deliver or mail all comments to: Ohio Environmental Protection Agency Attention: Division of Surface Water Permits Processing Unit P.O. Box 1049 Columbus, Ohio 43216-1049 The Ohio EPA permit number and Public Notice numbers should appear on each page of any submitted comments. All comments received no later than 30 days after the date of the Public Notice will be considered. Citizens may conduct file reviews regarding specific companies or sites. Appointments are necessary to conduct file reviews, because requests to review files have increased dramatically in recent years. The first 250 pages copied are free. For requests to copy more than 250 pages, there is a five-cent charge for each page copied. Payment is required by check or money order, made payable to Treasurer State of Ohio. For additional information about this fact sheet or the draft permit, contact Sara Hise, (614) 644-4824, sara.hise@epa.ohio.gov. Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -5- Location of Discharge/Receiving Water Use Classification The Duke Energy Ohio, Inc. Walter C. Beckjord Station (Beckjord) discharges to the Ohio River at Mile Point 528.2. Beckjord also discharges to Pond Run Creek and Tenmile Creek near their confluence with the Ohio River. Figure 1 shows the approximate location of the facility. This segment of the Ohio River is described by Ohio EPA River Code: 25-100, U.S. EPA River Reach #: 05030201, County: Clermont, Ecoregion: Interior Plateau. The Ohio River is designated for the following uses under Ohio’s WQS (Ohio Administrative Code [OAC] 3745-1-32): Warmwater Habitat (WWH), Agricultural Water Supply (AWS), Industrial Water Supply (IWS), Public Water Supply (PWS), and Bathing Waters (BW). Pond Run Creek and Tenmile Creek are designated for the following uses under OAC 3745-1-17: WWH, AWS, IWS, and Class B Primary Contact Recreation (PCR). Use designations define the goals and expectations of a waterbody. These goals are set for aquatic life protection, recreation use and water supply use, and are defined in the Ohio WQS (OAC 3745-1-07). The use designations for individual waterbodies are listed in rules -08 through -32 of the Ohio WQS. Once the goals are set, numeric WQS are developed to protect these uses. Different uses have different water quality criteria. Use designations for aquatic life protection include habitats for coldwater fish and macroinvertebrates, warmwater aquatic life and waters with exceptional communities of warmwater organisms. These uses all meet the goals of the federal CWA. Ohio WQS also include aquatic life use designations for waterbodies which cannot meet the CWA goals because of human-caused conditions that cannot be remedied without causing fundamental changes to land use and widespread economic impact. The dredging and clearing of some small streams to support agricultural or urban drainage is the most common of these conditions. These streams are given Modified Warmwater or Limited Resource Water designations. Recreation uses are defined by the depth of the waterbody and the potential for wading or swimming. Uses are defined for bathing waters, swimming/canoeing (PCR) and wading only (Secondary Contact - generally waters too shallow for swimming or canoeing). Water supply uses are defined by the actual or potential use of the waterbody. PWS designations apply near existing water intakes so that waters are safe to drink with standard treatment. Most other waters are designated for AWS and IWS. Facility Description Beckjord is a coal-fired steam electric generation station owned by Duke Energy Ohio, Inc. This facility is involved in the generation, transmission, and distribution of electric power. Beckjord’s processes generate wastewaters which are regulated by the federal effluent guidelines (FEGs) listed in 40 CFR 423, “Steam Electric Power Generating Point Source” Category. The process operations at this facility are also defined by the standard industrial classification (SIC) code 4911 – Electric Services. The facility has six power-generating units built between 1949 and 1969. Plans are underway to retire the power-generating units by the end of 2015, although some processes will still be active. Description of Existing Discharge Beckjord has several outfalls, which are described as follows: Outfall # 001 Wastewater Source Condenser cooling water, boiler blowdown, filter backwash, heat Treatment System Disinfection, dechlorination Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -6- Discharge Point Ohio River 005 exchangers Ash Pond B (North Ash Pond), Reverse osmosis, coal pile runoff, ash and pyrite conveying, drains, car rinse, ash landfill leachate collection Ash Pond C (South Ash Pond), drains, ash and pyrite conveying, boiler tube chemical cleaning, oil and grease separator Sanitary sewage treatment plant 006 007 008 009 010 Roof drainage collection tank #1 Roof drainage collection tank #2 Coal pile runoff emergency overflow Storm water Ash Pond C extension 011 012 013 014 016 017 018 019 020 021 022 023 024 025 Ash Pond C dike south leak collection Ash Pond C dike north leak collection Storm water Storm water Storm water Storm water Storm water Storm water Storm water Storm water Storm water Ground water interceptor well Coal pile runoff emergency overflow Storm water from Pond Run Ash Landfill Sedimentation Pond Storm water from Pond Run Ash Landfill (west side) Storm water from Pond Run Ash Landfill (east side) Boiler blowdown from Units 1 through 6 Effluent from boiler tube chemical waste treatment pond Discharge from miscellaneous heat exchangers (non-contact cooling water) 002 003 026 027 611 612 631 Sedimentation, flocculation/coagulation, neutralization, skimming Ohio River Sedimentation, flocculation/coagulation, neutralization, skimming Ohio River Aerobic digestion, activated sludge, disinfection None None None Oil/Water separator Sedimentation, neutralization, skimming None None None None None None None None None None None None None Sedimentation, skimming Ohio River Ohio River Ohio River Ohio River Ohio River Ohio River None pH adjustment, settling Pond Run Creek Pond Run Creek Pond Run Creek Pond Run Creek Ohio River Ohio River Ohio River Ohio River Ohio River Tenmile Creek Pond Run Creek Ohio River Ohio River Unnamed tributary of Pond Run Creek Unnamed tributary of Pond Run Creek Unnamed tributary of Pond Run Creek Outfall 001 Outfalls 002 and 003 Dechlorination Outfall 001 None None The approximate location of the outfalls is shown on Figure 2. Outfall 001 discharges the most wastewater of any outfall at the facility. The wastewater is composed primarily of condenser cooling water, with smaller amounts of boiler blowdown, filter backwash, and heat exchanger discharge. Intake water from the Ohio River is continuously chlorinated prior to use at the plant. Dechlorination is included in the treatment system prior to discharge at Outfall 001. Outfalls 002 and 003 receive wastewater from the North (“B”) and South (“C”) Ash Ponds, respectively. Wastewater is neutralized by lowering the pH as it enters the ponds. Solids settle to the bottom and oil and grease is skimmed off as the wastewater leaves the ponds. Beckjord Ash Pond A formerly discharged through Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -7- Outfall 004 to the Ohio River. However, the pond has been inactive since 1985, the last year the ash was sluiced there, and has not discharged since that time. Despite the absence of a discharge, Outfall 004 has remained in Beckjord's NPDES permit as a contingency, for dredging or other emergency ash storage. Based on current plant operations and historical non-use of the pond, Beckjord has determined that it will not need this contingency and the outfall is no longer required. Outfall 010 also discharges from the Ash Pond C, but it is not currently in use. Outfall 012 discharges wastewater collected from dike leaks surrounding Ash Pond C. The on-site sanitary sewerage treatment plant discharges through Outfall 005. The treatment system uses ultraviolet disinfection with chlorine as a back-up. Discharge is dechlorinated if chlorine is used. Contaminated groundwater is pumped through a groundwater interceptor well and discharged at Outfall 023. Outfalls 025 discharges landfill runoff from the Pond Run Ash Landfill sedimentation pond. The remainder of external outfalls are associated with storm water runoff. Runoff from roof drains is collected and discharged through outfalls 006 and 007. Waste oil from the primary oil/water separator collects in a below-ground storage tank while the wastewater flows through Outfall 009. Storm water from the Pond Run Ash Landfill flows through outfalls 025, 026, and 027. Storm water runoff from the closed landfill north of Beckjord Road discharges through Outfall 021. Outfalls 008, 009, 010, 011, 012, and 024 do not currently discharge. Beckjord has three active internal stations. Boiler blowdown discharges through internal station 611 and is sent to Outfall 001 without treatment. Boiler tube cleaning occurs every three to four years and is monitored at internal station 612. The boiler tubes are cleaned by introducing a weak organic acid to the tubes, which are then flushed with water and a caustic solution. The wastewater from this process is treated in a large aboveground tank by neutralization and the addition of a polymer to remove metals. The treated wastewater flows to the ash ponds for further settling. Internal station 631 discharges cooling water used to operate several large pumps and other equipment; the wastewater is sent through Outfall 001. Internal station 621 formerly monitored the regeneration waste stream. Beckjord no longer uses demineralizers and this station is no longer required. Beckjord obtains water from three sources. Most of the water is supplied by the Ohio River and used for condenser cooling water. On-site wells provide water from cooling transformers, boiler water, and other miscellaneous cooling activities. The local public water supply distribution system provides potable water. Consistent with 40 CFR 122.45(h), the current permit includes monitoring and limits at internal stations 611, 612, and 631. Effluent guideline limits are applied at these outfalls to ensure that these treatment standards are met prior to combining with other waste streams. If monitoring was not done at this location, it would not be possible to verify compliance with these standards due to dilution. Federal rules at 40 CFR 125.3(f) prohibit attaining these standards by dilution. Table 1 presents chemical specific data compiled from the NPDES renewal application Form 2C. Table 2 presents chemical specific data compiled from the Ohio EPA bioassay testing. Table 3 presents a summary of unaltered Discharge Monitoring Report (DMR) data. Data are presented for the period January 2008 through December 2012, and current permit limits are provided for comparison. Table 4 presents average and maximum PEQ values. Table 5 summarizes the acute toxicity results of Ohio EPA bioassay testing. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -8- Assessment of Impact on Receiving Waters In 2007, the Ohio River Valley Water Sanitation Commission (ORSANCO) conducted a biological survey in the Meldahl dam pool, which includes the Beckjord discharges. The survey showed that the biological condition of the pool is rated as “good” and that the entire pool meets its aquatic life-use designation. The complete report for the Meldahl pool can be found at this ORSANCO webpage: http://www.orsanco.org/images/stories/files/biologicalSurveys/2007/2007MeldahlPoolReport.pdf Further information on the Ohio River can be found in the 2012 Biennial Assessment of Ohio River Water Quality Conditions. The entire river is impaired for fish consumption due to polychlorinated biphenyl and dioxin contamination; potential impairment due to mercury has yet to be evaluated. This area is also only in partial attainment of the contact recreation use. More information can be found at this ORSANCO webpage: http://www.orsanco.org/images/stories/files/publications/305b/docs/2012/2012ohioriver305breport.pdf Development of Water-Quality-Based Effluent Limits Determining appropriate effluent concentrations is a multiple-step process in which parameters are identified as likely to be discharged by a facility, evaluated with respect to Ohio water quality criteria, and examined to determine the likelihood that the existing effluent could violate the calculated limits. Parameter Selection Effluent data for Beckjord were used to determine what parameters should undergo WLA. The parameters discharged are identified by the data available to Ohio EPA - Discharge Monitoring Report (DMR) data submitted by the permittee, compliance sampling data collected by Ohio EPA, and any other data submitted by the permittee, such as priority pollutant scans required by the NPDES application or by pretreatment, or other special conditions in the NPDES permit. The sources of effluent data used in this evaluation are as follows: Self-monitoring data (DMR) NPDES Application data Ohio EPA compliance sampling data January 2008 through December 2012 2013 2011 Outliers The data were examined, and the following values were removed from the evaluation to give a more reliable PEQ: Outfall 002 – mercury (96.5 ng/L on 12/1/09), Outfall 009 – zinc (879 µg/L on 3/3/08), total filterable residue (dissolved solids) (240 mg/L on 6/2/08, 11.65 mg/L on 5/3/10, 8.55 mg/L on 9/6/11). This data is evaluated statistically, and PEQ values are calculated for each pollutant. Average PEQ (PEQavg) values represent the 95th percentile of monthly average data, and maximum PEQ (PEQmax) values represent the 95th percentile of all data points. The average and maximum PEQ values are presented in Table 4. The PEQ values are used according to Ohio rules to compare to applicable WQS and allowable WLA values for each pollutant evaluated. Initially, PEQ values are compared to the applicable average and maximum WQS. If both PEQ values are less than 25 percent of the applicable WQS, the pollutant does not have the reasonable potential to cause or contribute to exceedances of WQS, and no WLA is done for that parameter. If either PEQavg or PEQmax is greater than 25 percent of the applicable WQS, a WLA is conducted to determine whether the parameter exhibits reasonable potential and needs to have a limit or if monitoring is required. See Table 9 for a summary of the screening results. Wasteload Allocation For those parameters that require a WLA, the results are based on the uses assigned to the receiving waterbody in OAC 3745-1. Dischargers are allocated pollutant loadings/concentrations based on the Ohio WQS (OAC 3745-1). Most pollutants are allocated by a mass-balance method because they do not degrade in the receiving Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -9- water. WLAs using this method are done using the following general equation: Discharger WLA = (downstream flow x WQS) - (upstream flow x background concentration). Discharger WLAs are divided by the discharge flow so that the allocations are expressed as concentrations. The applicable waterbody uses for this facility’s discharge and the associated stream design flows are as follows: Aquatic life (WWH) Toxics (metals, organics, etc.) Average Maximum AWS Human Health (carcinogens) Human Health (non-carcinogens) 10% of annual 7Q10 1% of annual 1Q10 10% of harmonic mean flow 10% of harmonic mean flow 100% of 7Q10 Allocations are developed using a percentage of stream design flow as specified in Table 7, and allocations cannot exceed the Inside Mixing Zone Maximum criteria. Ohio’s WQS implementation rules [OAC 3745-2-05(A)(2)(d)(iv)] required a phase out of mixing zones for bioaccumulative chemicals of concern (BCCs) as of November 15, 2010. This rule applied statewide. Mercury is a BCC. The mixing zone phase-out means that as of November 15, 2010 all dischargers requiring mercury limits in their NPDES permit must meet WQS at the end-of-pipe, which are 12 ng/l (average) and 1700 ng/l (maximum) in the Ohio River basin. A WLA has been calculated for thermal loading at Outfall 001. The thermal WLA was calculated using this equation: BTU/hr = (7Q10 * percent of stream flow of 001 * conversion factor of cfs to MGD * conversion factor of gallons to pounds * temperature difference in °F)/24 The average design flow at Outfall 001 is approximately 10% of the Ohio River’s 7Q10 flow rate. The conversion of cubic feet/second (cfs) to MGD is 0.646. The conversion of gallons to pounds is 8.34. The temperature difference is the difference between the 2012 ORSANCO pollution control standards maximum temperature minus the average of the daily maximum intake temperatures at the facility. A conversion factor of 24 hours per day is also applied. The seasonal facility averages were calculated using the intake temperature data from January 2012 to December 2012. The thermal WLA for the mixing zone is: Season Summer Winter Facility Intake (°F) 82 54 ORSANCO Max (°F) 89 60 Thermal Load (BTU/hr) 1675 1435 Beckjord’s PEQavg is 2525 BTU/hr and it’s PEQmax is is 3461 BTU/hr. Both of these are greater than the available thermal loading of the Ohio River as shown by the above calculation. Beckjord therefore has reasonable potential to exceed temperature standards on the Ohio River. The data used in the WLA are listed in Tables 6 and 7. The WLA results to maintain all applicable criteria are presented in Table 8. Whole Effluent Toxicity WLA Whole effluent toxicity (WET) is the total toxic effect of an effluent on aquatic life measured directly with a toxicity test. Acute WET measures short term effects of the effluent while chronic WET measures longer term and potentially more subtle effects of the effluent. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -10- WQS for WET are expressed in Ohio’s narrative “free from” WQS rule [OAC 3745-1-04(D)]. These “free froms” are translated into toxicity units (TUs) by the associated WQS Implementation Rule (OAC 3745-2-09). WLAs can then be calculated using TUs as if they were water quality criteria. The WLA calculations for WET are similar to those for aquatic life criteria - using the chronic toxicity unit (TUc) and 7Q10 flow for the average and the acute toxicity unit (TUa) and 1Q10 flow for the maximum. These values are the levels of effluent toxicity that should not cause instream toxicity during critical low-flow conditions. For Beckjord, the WLA values are: Outfall 002: 1.0 TUa and 161 TUc Outfall 003: 1.0 TUa and 58 TUc Outfall 005: 1.0 TUa and 341936 TUc Outfall 009: 1.0 TUa and 58 TUc Outfall 012: 1.0 TUa and 706667 TUc Outfall 023: 1.0 TUa and 2677 TUc Outfall 025: 0.3 TUa and 1.0 TUc The chronic toxicity unit (TUc) is defined as 100 divided by the estimate of the effluent concentration which causes a 25% reduction in growth or reproduction of test organisms (IC25): TUc = 100/IC25 This equation applies outside the mixing zone for warmwater, modified warmwater, exceptional warmwater, coldwater, and seasonal salmonid use designations except when the following equation is more restrictive (Ceriodaphnia dubia only): TUc = 100/geometric mean of No Observed Effect Concentration and Lowest Observed Effect Concentration The acute toxicity unit (TUa) is defined as 100 divided by the concentration in water having 50% chance of causing death to aquatic life (LC50) for the most sensitive test species: TUa = 100/LC50 This equation applies outside the mixing zone for warmwater, modified warmwater, exceptional warmwater, coldwater, and seasonal salmonid use designations. When the acute WLA is less than 1.0 TUa, it may be defined as: Dilution Ratio (downstream flow to discharger flow) Allowable Effluent Toxicity (percent effects in 100% effluent) up to 2 to 1 greater than 2 to 1 but less than 2.7 to 1 2.7 to 1 to 3.3 to 1 30 40 50 The acute WLA for the is 30 percent mortality in 100 percent effluent based on the dilution ratio of 2 to 1. Reasonable Potential/ Effluent Limits/Hazard Management Decisions After appropriate effluent limits are calculated, the reasonable potential of the discharger to violate the WQS must be determined. Each parameter is examined and placed in a defined "group". Parameters that do not have Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -11- a WQS or do not require a WLA based on the initial screening are assigned to either group 1 or 2. For the allocated parameters, the preliminary effluent limits (PEL) based on the most restrictive average and maximum WLAs are selected from Table 6. The average PEL (PELavg) is compared to the average PEQ (PEQavg) from Table 4, and the PELmax is compared to the PEQmax. Based on the calculated percentage of the allocated value [(PEQavg ÷ PELavg) X 100, or (PEQmax ÷ PELmax) X 100)], the parameters are assigned to group 3, 4, or 5. The groupings are listed in Table 9. The final effluent limits are determined by evaluating the groupings in conjunction with other applicable rules and regulations. Table 10 presents the final effluent limits and monitoring requirements proposed for Beckjord Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 and the basis for their recommendation. Outfall 001 Water Temperature, Flow Rate, and Station Operating Input Monitoring for these parameters is proposed to continue. Data from these parameters are utilized for thermal loading and mass loading limit calculations. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. Thermal Discharge The thermal load limits for Outfall 001 are based on the Beckjord’s Clean Water Act 316(a) demonstration. This thermal limit is still appropriate because the number of units discharging oncethrough cooling water have not changed since the demonstration was performed. Even though the thermal limit exceeds the thermal WLA, this section of the Ohio River is meeting its attainment criteria, indicating that a higher thermal load is not adversely impacting the stream ecology. Chlorination/Bromination Duration and Chlorine – Total Residual Limits for these parameters are required by the FEGs in 40 CFR 423 and listed in Attachment 1. Continuous chlorination is necessary at Beckjord; therefore, it is proposed that the limit of total residual chlorine at the WQS be continued. Outfall 002 Flow Rate Monitoring is proposed to continue. Data is utilized for mass loading limit calculations. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. Total Suspended Solids and Oil & Grease Limits for oil & grease are proposed to continue from the existing permit. The limits are based on the best practicable control technology currently available (BPT) FEGs in 40 CFR 423.12(b)(4) and are listed in Attachment 1. The average limit for total suspended solids (TSS) is also proposed to be continued. The maximum limits for TSS is proposed to be lowered slightly. Coal pile runoff, which discharges to Outfall 002, is subject to 40 CFR 423.12(b)(9), which is listed in Attachment 1. To account for the lower TSS limit for coal pile runoff (50 mg/L), the following calculations were performed to determine the appropriate flow-weighted concentration: Cwgt = [ (Qw * 100) + (Qc * 50) ] / Qmax Where: Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -12- Cwgt = the flow-weighted concentration Qw = maximum flow rate of wastewater without the coal pile runoff flow rate (Qmax – Qc) Qc = maximum flow rate of coal pile runoff Qmax = maximum flow rate of Outfall 002 Maximum flow rates were based on the values presented on the water balance diagram included in the facility’s NPDES permit renewal application. The maximum flow rate for the coal pile runoff was utilized because in nearly all cases all runoff will be eventually routed to Outfall 002. Cwgt = [ (3.865 MGD *100 mg/L) + (0.03 MGD * 50 mg/L) ] / 3.865 MGD = 99.6 mg/L The maximum TSS loading limit will decrease slight based on the new proposed TSS concentration limit. Cadmium, Chlorine – Total Residual, Iron, Lead, Molybdenum, Sulfates, Strontium, Zinc The Ohio EPA risk assessment (Table 9) places these parameters in group 3. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. No monitoring is proposed. Barium, Boron, and Iron The Ohio EPA risk assessment (Table 9) places these parameters in group 3. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring at a low frequency of once per quarter is proposed to document that these pollutants continue to remain at low levels. Mercury Ohio EPA risk assessment (Table 9) places this parameter in group 4. This placement, as well as the data in Tables 1 - 4, supports that this parameter does not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring for Group 4 pollutants (where PEQ exceeds 50 percent of the WLA) is required by OAC 3745-33-07(A)(2). The monitoring frequency is proposed to be increased to once per month. Copper The Ohio EPA risk assessment (Table 9) places this parameter in group 5. This placement, as well as the data in Tables 1 - 4, indicates that the reasonable potential to exceed WQS exists and limits are necessary to protect water quality. For this parameter, the PEQ is greater than 100 percent of the WLA. Pollutants that meet this requirement must have permit limits under OAC 3745-33-07(A)(1). A maximum daily concentration and loading limit are proposed. Outfall 003 Flow Rate Monitoring is proposed to continue. Data is utilized for mass loading limit calculations. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. Total Suspended Solids and Oil & Grease Limits for TSS and oil & grease are proposed to continue from the existing permit. The concentration limits are based on BPT FEGs in 40 CFR 423.12(b)(4) and listed in Attachment 1. Loading limits are proposed to remain the same as in the previous permit due to anti-backsliding rules. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -13- Aluminum, Arsenic, Barium, Chlorine – Total Residual, Iron, Magnesium, Molybdenum, Strontium, Total Filterable Residue (dissolved solids), Vanadium, and Zinc The Ohio EPA risk assessment (Table 9) places these parameters in groups 1, 2, or 3. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. No monitoring is proposed. Mercury The Ohio EPA risk assessment (Table 9) places this parameter in group 3. This placement, as well as the data in Tables 1 - 4, supports that this parameter does not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring at a low frequency is proposed to document that this pollutant continues to remain at low levels. Copper Ohio EPA risk assessment (Table 9) places this parameter in group 4. This placement, as well as the data in Tables 1 - 4, supports that this parameter does not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring for Group 4 pollutants (where PEQ exceeds 50 percent of the WLA) is required by OAC 3745-33-07(A)(2). The monitoring frequency is proposed to be increased to once per month. Outfall 005 Color, Odor, and Turbidity Severity Monitoring for color and odor severity is proposed to be removed based on updated guidance documents for sanitary sewage monitoring. Monitoring for turbidity severity will continue. Flow Rate Monitoring is proposed to continue. Data is utilized for mass loading limit calculations. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. Total Suspended Solids and Carbonaceous Biochemical Oxygen Demand (5-day) Limits for these two parameters are based on plant design and are proposed to continue. Fecal Coliform and E. Coli New E. coli limits are being proposed based on ORSANCO’s 2012 pollution control standards. These limits will be in effect from April to October. The winter fecal coliform limits are based on WQS and are proposed to continue for the months of November through March. Based on best engineering judgment, it is expected the facility will be able to comply with the new limits without a schedule of compliance. Zinc Ohio EPA risk assessment (Table 9) places this parameter in group 4. This placement, as well as the data in Tables 1 - 4, supports that this parameter does not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring for Group 4 pollutants (where PEQ exceeds 50 percent of the WLA) is required by OAC 3745-33-07(A)(2). The monitoring frequency is proposed to be increased to once per month. Mercury Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -14- The Ohio EPA risk assessment (Table 9) places mercury in group 5, which recommends limits to protect water quality. Using the discretion allowed the Director under OAC 3745-33-07(A)(5), monitoring instead of limits is being proposed. The PEQ values calculated for mercury (Table 4) may not be representative of its actual levels in the plant effluent as they were based on four data points. The purpose of the proposed monitoring is to collect additional data on the frequency of occurrence and variability of these pollutants in the plant’s effluent. Copper The Ohio EPA risk assessment (Table 9) places this parameter in group 5. This placement, as well as the data in Tables 1 - 4, indicates that the reasonable potential to exceed WQS exists and limits are necessary to protect water quality. For this parameter, the PEQ is greater than 100 percent of the WLA. Pollutants that meet this requirement must have permit limits under OAC 3745-33-07(A)(1). A maximum daily concentration and loading limit are proposed. Outfall 009 Flow Rate Monitoring is proposed to continue. Data is utilized for mass loading limit calculations. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. Oil & Grease Limits are based on FEGs for low-volume wastewater listed in 40 CFR 423 and are proposed to continue. Iron and Sulfates Ohio EPA risk assessment (Table 9) places these parameters in groups 2 and 3. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring is not proposed. Zinc The Ohio EPA risk assessment (Table 9) places this parameter in group 3. This placement, as well as the data in Tables 1 - 4, supports that this parameter does not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Limits are proposed to be removed and monitoring at a low frequency is proposed to document that this pollutant continues to remain at low levels. Outfall 012 Flow Rate Monitoring is proposed to continue. Data is utilized for mass loading limit calculations. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. Total Suspended Solids and Oil & Grease Concentration limits for TSS and oil & grease are proposed to continue from the existing permit. Loading limits are proposed to be removed. Discharge at this outfall is intermittent and it has not discharged in the past five years. The concentration limits are based on the best practicable control technology currently available (BPT) FEGs in 40 CFR 423.12(b)(4). Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -15- Arsenic, Barium, Chlorine – Total Residual, Molybdenum, Sulfates, Strontium, and Vanadium The Ohio EPA risk assessment (Table 9) places these parameters in groups 2 or 3. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring for strontium is proposed to be removed and no new monitoring is proposed. Total Filterable Residue (Dissolved Solids) and Zinc. The Ohio EPA risk assessment (Table 9) places these parameters in group 3. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Limits for total filterable residue are proposed to be removed and monitoring at a low frequency is proposed to document that both pollutants continue to remain at low levels. Mercury Ohio EPA risk assessment (Table 9) places this parameter in group 4. This placement, as well as the data in Tables 1 - 4, supports that this parameter does not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring for Group 4 pollutants (where PEQ exceeds 50 percent of the WLA) is required by OAC 3745-33-07(A)(2). The monitoring frequency is proposed to be increased to once per month. Copper The Ohio EPA risk assessment (Table 9) places this parameter in group 5. This placement, as well as the data in Tables 1 - 4, indicates that the reasonable potential to exceed WQS exists and limits are necessary to protect water quality. For this parameter, the PEQ is greater than 100 percent of the WLA. Pollutants that meet this requirement must have permit limits under OAC 3745-33-07(A)(1). The maximum daily concentration in the WLA is higher than the current permit limit. Due to antibacksliding rules, the current limits are proposed to continue. Outfall 023 Flow Rate Monitoring is proposed to continue. Data is utilized for mass loading limit calculations. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. Antimony, Boron, Sulfates, and Zinc The Ohio EPA risk assessment (Table 9) places these parameters in groups 2 or 3. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. No monitoring is proposed. Outfall 025 Flow Rate and Total Precipitation Monitoring is proposed to continue. pH The limits from the existing limits are proposed to continue. The outside mixing zone WQS of 6.5 to 9.0 S.U. is maintained in the receiving stream. TSS Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -16- Limits are based on FEGs for low-volume wastewater listed in 40 CFR 423 and are proposed to continue. Boron, Iron, Manganese, Molybdenum, and Phosphorus The Ohio EPA risk assessment (Table 9) places these parameters in groups 1 or 2. This placement, as well as the data in Tables 1 - 4, support that these parameters do not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. No new monitoring is proposed, and monitoring for boron is proposed to be removed. Mercury Ohio EPA risk assessment (Table 9) places this parameter in group 4. This placement, as well as the data in Tables 1 - 4, supports that this parameter does not have the reasonable potential to contribute to WQS exceedances, and limits are not necessary to protect water quality. Monitoring for Group 4 pollutants (where PEQ exceeds 50 percent of the WLA) is required by OAC 3745-33-07(A)(2). The monitoring frequency is proposed to be increased to once per quarter. Arsenic, Barium, and Zinc The Ohio EPA risk assessment (Table 9) places these parameters in group 5, which recommends limits to protect water quality. Using the discretion allowed the Director under OAC 3745-33-07(A)(5), monitoring instead of limits is being proposed. The PEQ values calculated for these parameters (Table 4) may not be representative of its actual levels in the plant effluent as they were based on one data point for each parameter. The purpose of the proposed monitoring is to collect additional data on the frequency of occurrence and variability of these pollutants in the plant’s effluent. Whole Effluent Toxicity Reasonable Potential Based on evaluating the whole effluent toxicity (WET) data presented in Table 5 and other pertinent data under the provisions of OAC 3745-33-07(B), Beckjord is placed in Category 4 with respect to WET. No monitoring is proposed. Internal Stations Monitoring and limits are proposed at internal stations 611, 612, and 631. Effluent guideline limits are applied at this outfall to ensure that these treatment standards are met prior to combining with other waste streams. If monitoring was not done at this location, it would not be possible to verify compliance with these standards due to dilution. Federal rules at 40 CFR 125.3(f) prohibit attaining these standards by dilution. All limits are based upon 40 CFR 423. FEGs applicable to these stations are listed in Attachment 1. Other Requirements Compliance Schedule A schedule of compliance is included in Part I.C for meeting new copper limits at outfalls 002 and 005. Operator Certification Operator certification requirements have been included in Part II of the permit in accordance with rules adopted in December 2006. These rules require the Beckjord to have a Class A wastewater treatment plant operator in charge of the sewage treatment plant operations discharging through outfall 005. Operator of Record In December 2006, OAC rule revisions became effective that affect the requirements for certified operators for sewage collection systems and treatment works regulated under NPDES permits. Part II of this NPDES permit is included to implement OAC 3745-7-02. It requires the permittee to designate one or more operator of record to oversee the technical operation of the treatment works. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -17- Public Water Supply Notice An addition to rule 3745-33-08 of the OAC requires that permittees discharging wastewater within ten miles of a downstream public water supply intake located on the same waterway, must develop spill (or bypass) notification procedures in conjunction with the downstream public water supply operator. Since the City of Cincinnati operates a public water supply intake less than ten miles downstream from Beckjord, Part II of the draft permit requires the development of notification procedures within six months after the effective date of the permit. Storm Water Compliance Parts IV, V, and VI have been included with the draft permit in order to ensure that any storm water flows from the facility site are properly regulated and managed. As an alternative to complying with Parts IV, V, and VI, Beckjord may seek permit coverage under the general permit for industrial stormwater (permit # OHR000005) or submit a “No Exposure Certification.” Parts IV, V, and VI will be removed from the final permit if: 1) Beckjord submits a Notice of Intent (NOI) for coverage under the general permit for industrial stormwater or submits a No Exposure Certification, 2) Ohio EPA determines that the facility is eligible for coverage under the general permit or meets the requirements for a No Exposure Certification, and 3) the determination by Ohio EPA can be made prior to the issuance of the final permit. Parts IV, V, and VI have been updated to make individual permits consistent with Ohio EPA's Industrial Storm Water General Permit. The language includes more detail on storm water pollution prevention requirements, and benchmark values that define the goals of pollution prevention efforts. These are not discharge limitations; if pollution prevention measures cannot achieve the benchmarks, the facility may provide information to document this. Outfall Signage Part II.P of the permit includes requirements for the permittee to maintain a sign at each permitted outfall to the Ohio River, Tenmile Creek, and unnamed tributary of Pond Run Creek providing information about the discharge. Signage at outfalls is required pursuant to OAC 3745-33-08(A). Section 316(a) Compliance A schedule of compliance to update the Section 316(a) demonstration is presented in Part I.C of the permit. Section 316(b) Compliance Under rules which were promulgated July 9, 2004 under Section 316(b) of the federal Clean Water Act (33 United States Code [USC] section 1326), the permittee was required to collect and/or compile the following information pertaining to the facility’s cooling water intake structure(s): - source water physical data [40 CFR 122.21(r)(2)]; - cooling water intake structure data [40 CFR 122.21(r)(3)]; - cooling water system data [40 CFR 122.21(r)(5)]; and - rates of impingement and/or entrainment of fish and shellfish at the facility’s cooling water intake structure(s) based upon sampling conducted at the facility. The permit requires all of this information listed above to be submitted with the permittee’s next NPDES permit renewal application unless federal rules are promulgated which require the submittal of the information at an earlier date. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -18- Figure 1. Approximate Location of Duke Energy Inc., Beckjord Station Beckjord Station Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -19- Figure 2. Approximate Location of Beckjord Outfalls Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -20- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Outfall 001 Biological Oxygen Demand Chemical Oxygen Demand Total Organic Carbon Total Suspended Solids Ammonia Flow Rate Temperature-Winter Temperature-Summer pH Aluminum Antimony Arsenic Barium Beryllium Boron Bromide Cadmium Chlorine, Total Residual Chromium Cobalt Copper Cyanide Fluoride Iron Lead Magnesium Manganese Mercury Molybdenum Nickel Nitrate+Nitrite Oil & Grease Phenols Phosphorus Units Conc Mass Effluent Max daily 30 day max Conc Mass Conc Mass Intake Long term avg Conc Mass mg/L lb/day < 2.0 < 9395 - - < 2.0 < 12663 mg/L mg/L lb/day lb/day < 20 3.1 < 93950 14562 - - < 20 3.1 < 126626 19627 mg/L mg/L MGD °F °F S.U. mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day 6 < 2.0 28185 < 9395 - - < 4.0 < 2.0 < 25325 < 12663 563 85.1 81.1 7.42 - 8.0 0.26 1221 < 0.002 < 9.4 < 0.005 < 23 0.054 254 < 0.001 < 4.7 0.13 611 < 0.50 < 2349 < 0.001 < 4.7 - 490 85.1 81.1 7.42 - 8.0 - mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L ng/L mg/L mg/L mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day 0.038 < 0.002 < 0.001 0.0036 < 0.01 < 1.0 0.35 0.0028 14 0.036 1.7 0.0048 0.0021 0.607 < 4.7 < 0.04 < 0.1 179 < 9.4 < 4.70 17 < 47 < 4697 1644 13 65765 169 0.008 22.5 9.9 2851 < 22078 < 188 < 470 0.038 - 155 - Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -21- 759 0.29 < 0.002 < 0.005 0.053 < 0.001 0.14 <0.5 < 0.001 1836 < 13 < 32 336 < 6.3 886 <3166 < 6.3 < 0.01 < 0.002 < 0.001 < 0.002 < 0.01 < 1.0 0.48 < 0.001 14 0.042 4.85 0.0061 < 0.002 0.595 < 5.1 < 0.04 < 0.1 < 63 < 13 < 6.3 < 13 < 63 < 6331 3039 < 6.3 88638 266 0.0307 39 < 13 3767 < 32290 < 253 < 633 Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Selenium Silver Sulfate Sulfide Sulfite Surfactants Thallium Tin Titanium Total Organic Nitrogen Zinc Outfall 002 Biological Oxygen Demand Chemical Oxygen Demand Total Organic Carbon Total Suspended Solids Ammonia Flow Rate Temperature-Winter Temperature-Summer pH Aluminum Antimony Arsenic Barium Beryllium Boron Bromide Cadmium Chlorine, Total Residual Chromium Cobalt Copper Units Conc Mass mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day Effluent Max daily 30 day max Conc Mass Conc Mass < 0.005 < 23 < 0.001 < 4.7 100 469750 < 1.0 <4697 < 0.5 < 2349 < 0.03 < 141 < 0.002 < 9.4 < 0.01 < 47 < 0.01 < 47 - Intake Long term avg Conc Mass < 0.005 < 32 < 0.001 < 6.3 100 633130 <1 < 6331 < 0.5 < 3166 < 0.03 < 190 < 0.002 < 13 < 0.01 < 63 < 0.01 < 63 mg/L mg/L lb/day lb/day < 3.0 < 0.01 < 14092 < 47 - - <3 < 0.01 < 18994 < 63 mg/L lb/day < 2.0 < 58 - - < 2.0 < 12663 mg/L mg/L lb/day lb/day < 20 2.2 < 583 64 - - < 20 3.1 < 126626 19627 mg/L mg/L MGD °F °F S.U. mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day 18.6 < 2.0 542 < 58 - - < 4.0 < 2.0 < 25325 < 12663 3.49 NA 74.8 7.36-8.19 0.35 10.2 < 0.002 < 0.058 < 0.005 < 0.15 0.118 3.44 < 0.001 < 0.029 4.01 117 <0.05 < 15 < 0.001 < 0.029 7.36-8.19 0.118 3.44 4.01 117 - 0.29 < 0.002 < 0.005 0.053 < 0.001 0.14 < 0.5 < 0.001 1836 < 13 < 32 336 < 6.3 886 < 3166 < 6.3 mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day < 0.01 < 0.002 < 0.001 0.0105 0.0105 < 0.01 < 0.002 < 0.001 < 0.002 < 63 < 13 < 6.3 < 13 < 0.29 < 0.058 < 0.029 0.306 3.49 NA - 0.306 759 NA - - Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -22- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Cyanide Fluoride Iron Lead Magnesium Manganese Mercury Molybdenum Nickel Nitrate+Nitrite Oil & Grease Phenols Phosphorus Selenium Silver Sulfate Sulfide Sulfite Surfactants Thallium Tin Titanium Total Organic Nitrogen Zinc Outfall 003 Biological Oxygen Demand Chemical Oxygen Demand Total Organic Carbon Total Suspended Solids Ammonia Flow Rate Temperature-Winter Temperature-Summer pH Units Conc Mass mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day ng/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day Effluent Max daily Conc Mass < 0.01 < 0.29 < 1.0 < 29 1.68 49 < 0.001 < 0.029 19 553 0.17 4.95 2.4 0.00007 0.014 0.408 0.0037 0.11 0.244 7.11 < 5.0 < 146 < 0.04 < 1.2 < 0.1 < 2.9 0.005 0.15 < 0.001 < 0.03 170 4952 < 1.0 < 29 < 0.5 < 15 < 0.03 < 0.874 < 0.002 < 0.06 < 0.01 < 0.291 0.015 0.437 mg/L mg/L lb/day lb/day < 3.0 < 0.01 < 87 < 0.29 - - < 3.0 < 0.001 < 18994 < 6.3 mg/L lb/day < 2.0 < 200 - - < 2.0 < 12663 mg/L mg/L lb/day lb/day < 20 1.6 < 2002 160 - - < 20 3.1 < 126626 19627 mg/L mg/L MGD °F °F S.U. lb/day lb/day - 19.6 < 2.0 1961 < 200 19.6 - 1961 - < 4.0 < 2.0 < 25325 < 12663 12 NA 75.6 7.26-8.95 30 day max Conc Mass 1.68 49 2.4 0.00007 < 5.0 < 146 - 12 NA 7.26-8.95 Intake Long term avg Conc Mass < 0.001 < 6.3 < 1.0 < 6331 0.48 3039 < 0.001 < 6.3 14 88638 0.042 266 4.85 0.0307 0.0061 39 < 0.002 < 13 0.595 3767 < 5.1 < 32390 < 0.04 < 253 < 0.1 < 633 < 0.005 < 32 < 0.001 < 6.3 100 633130 < 1.0 < 6331 < 0.5 < 3166 < 0.03 < 190 < 0.002 < 13 < 0.01 < 63 < 0.01 < 63 759 NA - Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -23- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Aluminum Antimony Arsenic Barium Beryllium Boron Bromide Cadmium Chlorine, Total Residual Chromium Cobalt Copper Cyanide Fluoride Iron Lead Magnesium Manganese Mercury Molybdenum Nickel Nitrate+Nitrite Oil & Grease Phenols Phosphorus Selenium Silver Sulfate Sulfide Sulfite Surfactants Thallium Tin Titanium Total Organic Nitrogen Zinc Units Conc Mass mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day Effluent Max daily 30 day max Conc Mass Conc Mass 1.6 160 0.0057 0.57 0.024 2.4 0.13 13 < 0.001 < 0.1 2.1 210 < 0.5 < 50 < 0.001 < 0.1 - Intake Long term avg Conc Mass 0.29 1836 < 0.002 < 13 < 0.005 < 32 0.053 336 < 0.001 < 6.3 0.14 886 < 0.5 < 3166 < 0.001 < 6.3 mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L ng/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day < 0.01 0.021 < 0.001 0.0051 < 0.01 < 1.0 0.3 0.0013 13 0.0084 3.1 0.3 0.0023 0.431 69.5 < 0.04 < 0.1 0.017 < 0.001 200 < 1.0 < 0.5 < 0.03 0.0028 < 0.01 0.023 < 1.0 2.1 < 0.1 0.51 <1 < 100 30 0.13 1301 0.84 0.00031 30 0.23 43.1 6955 4 < 10 1.7 < 0.1 20015 < 100 < 50 < 3.0 0.28 < 1.0 2.3 3.1 69.5 - 0.00031 6955 - < 0.01 < 0.002 < 0.001 < 0.002 < 0.001 < 1.0 0.48 < 0.001 14 0.042 4.85 0.0061 < 0.002 0.595 < 5.1 < 0.04 < 0.1 < 0.005 < 0.001 100 < 1.0 < 0.5 < 0.03 < 0.002 < 0.01 < 0.01 < 63 < 13 < 6.3 < 13 < 6.3 < 6331 3039 < 6.3 88638 266 0.0307 39 < 13 3767 < 32390 < 253 < 633 < 32 < 6.3 633130 < 6331 < 3166 < 190 < 13 < 63 < 63 mg/L mg/L lb/day lb/day < 3.0 < 0.01 < 300 <1 - - < 3.0 < 0.001 < 18994 < 6.3 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -24- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Outfall 005 Biological Oxygen Demand Chemical Oxygen Demand Total Organic Carbon Total Suspended Solids Ammonia Flow Rate Temperature-Winter Temperature-Summer pH Aluminum Antimony Arsenic Barium Beryllium Boron Bromide Cadmium Chlorine, Tot Res Chromium Cobalt Copper Cyanide Fluoride Iron Lead Magnesium Manganese Mercury Molybdenum Nickel Nitrate+Nitrite Oil & Grease Phenols Units Conc Mass Effluent Max daily 30 day max Conc Mass Conc Mass Intake Long term avg Conc Mass mg/L lb/day < 2.0 < 0.1 - - < 2.0 < 12663 mg/L mg/L lb/day lb/day < 20 3.3 < 0.83 0.14 - - < 20 3.1 < 126626 19627 mg/L mg/L MGD °F °F S.U. mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L ng/L mg/L mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day 20.5 < 2.0 0.856 < 0.08 20.5 - < 4.0 < 2.0 < 25325 < 12663 0.005 NA 75.4 7.0 - 7.81 0.05 0.0021 < 0.002 < 0.00008 < 0.005 < 0.00021 0.017 0.00071 < 0.001 < 0.00004 0.12 0.00501 < 0.5 < 0.02 < 0.001 < 0.00004 < 0.01 < 0.004 < 0.002 < 0.0001 < 0.001 < 0.00004 0.022 0.0009 < 0.01 < 0.00042 < 1.0 < 0.042 0.29 0.0121 0.0011 0.00005 12 0.5008 0.024 0.001 29 0.000001 0.011 0.00046 < 0.002 < 0.00008 18.3 0.764 < 4.7 < 0.2 < 0.04 < 0.0017 0.405 0.002 NA 7.0 - 7.81 0.022 0.0004 - 759 NA 0.29 < 0.002 < 0.005 0.053 < 0.001 0.14 < 0.5 < 0.001 < 0.01 < 0.002 < 0.001 < 0.002 < 0.001 < 1.0 0.48 < 0.001 14 0.042 4.85 0.0061 < 0.002 0.595 < 5.1 < 0.04 1836 < 13 < 32 336 < 6.3 886 < 3166 < 6.3 < 63 < 13 < 6.3 < 13 < 6.3 < 6331 3039 < 6.3 88638 266 0.0307 39 < 13 3767 < 32390 < 253 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -25- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Phosphorus Selenium Silver Sulfate Sulfide Sulfite Surfactants Thallium Tin Titanium Total Organic Nitrogen Zinc Outfall 023 Biological Oxygen Demand Chemical Oxygen Demand Total Organic Carbon Total Suspended Solids Ammonia Flow Rate Temperature-Winter Temperature-Summer pH Aluminum Antimony Arsenic Barium Beryllium Boron Bromide Cadmium Chlorine, Total Residual Chromium Cobalt Units Conc Mass mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day Effluent Max daily 30 day max Conc Mass Conc Mass 1.7 0.071 < 0.005 < 0.00021 < 0.001 < 0.00004 75 3.1 < 1.0 < 0.042 < 0.5 < 0.02 < 0.03 < 0.00125 < 0.002 < 0.0001 < 0.01 < 0.00042 < 0.01 < 0.00042 - Intake Long term avg Conc Mass < 0.1 < 633 < 0.005 < 32 < 0.001 < 6.3 100 633130 < 1.0 < 6331 < 0.5 < 3166 < 0.03 < 190 < 0.002 < 13 < 0.01 < 63 < 0.01 < 63 mg/L mg/L lb/day lb/day < 3.0 0.131 < 0.13 0.005 - - < 3.0 < 0.001 < 18994 < 6.3 mg/L lb/day < 2.0 < 4.1 - - < 2.0 < 12663 mg/L mg/L lb/day lb/day < 20 < 1.0 < 41 < 2.0 - - < 20 3.1 < 126626 19627 mg/L mg/L MGD °F °F S.U. mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day < 4.0 < 2.0 < 8.1 < 4.1 - < 4.0 < 2.0 < 25325 < 12663 0.244 NA 64.8 7.34 - 7.83 < 0.05 < 0.1 < 0.002 < 0.0041 < 0.005 < 0.01 0.029 0.059 < 0.001 < 0.002 1.1 2.24 < 0.5 < 1.0 < 0.001 < 0.002 - - 0.29 < 0.002 < 0.005 0.053 < 0.001 0.14 < 0.5 < 0.001 1836 < 13 < 32 336 < 6.3 886 < 3166 < 6.3 mg/L mg/L mg/L lb/day lb/day lb/day < 0.01 < 0.002 < 0.001 - - < 0.01 < 0.002 < 0.001 < 63 < 13 < 6.3 < 0.02 < 0.0041 < 0.002 759 NA NA Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -26- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Copper Cyanide Fluoride Iron Lead Magnesium Manganese Mercury Molybdenum Nickel Nitrate+Nitrite Oil & Grease Phenols Phosphorus Selenium Silver Sulfate Sulfide Sulfite Surfactants Thallium Tin Titanium Total Organic Nitrogen Zinc Outfall 025 Biological Oxygen Demand Chemical Oxygen Demand Total Organic Carbon Total Suspended Solids Ammonia Flow Rate Temperature-Winter Temperature-Summer Units Conc Mass mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day ng/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day Effluent Max daily 30 day max Conc Mass Conc Mass < 0.002 < 0.0041 < 0.001 < 0.002 < 1.0 < 2.0 < 0.05 < 0.01 < 0.001 < 0.002 12 24.439 0.099 0.2 < 0.5 <0.000001 0.016 0.033 < 0.002 < 0.0041 0.254 0.517 < 4.8 < 9.8 < 0.04 < 0.081 < 0.1 < 0.2 < 0.005 < 0.01 < 0.001 < 0.002 160 326 < 1.0 < 2.0 < 0.5 < 1.0 < 0.03 < 0.0611 < 0.002 < 0.0041 < 0.01 < 0.02 < 0.01 < 0.02 - Intake Long term avg Conc Mass < 0.002 < 13 < 0.001 < 6.3 < 1.0 < 6331 0.48 3039 < 0.001 < 6.3 14 88638 0.042 266 4.85 0.0307 0.0061 39 < 0.002 < 13 0.595 3767 < 5.1 < 32390 < 0.04 < 253 < 0.1 < 633 < 0.005 < 32 < 0.001 < 6.3 100 633130 < 1.0 < 6331 < 0.5 < 3166 < 0.03 < 190 < 0.002 < 13 < 0.01 < 63 < 0.01 < 63 mg/L mg/L lb/day lb/day < 3.0 < 0.001 < 6.1 < 0.002 - - < 3.0 < 0.001 < 18994 < 6.3 mg/L lb/day < 2.0 < 2.9 - - < 2.0 < 12663 mg/L mg/L lb/day lb/day 20 6.2 29 9 - - < 20 3.1 < 126626 19627 mg/L mg/L MGD °F °F lb/day lb/day - 64 <2 92.9 < 2.9 - - < 4.0 < 2.0 < 25325 < 12663 0.174 NA 83.8 NA - 759 NA - Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -27- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter pH Aluminum Antimony Arsenic Barium Beryllium Boron Bromide Cadmium Chlorine, Total Residual Chromium Cobalt Copper Cyanide Fluoride Iron Lead Magnesium Manganese Mercury Molybdenum Nickel Nitrate+Nitrite Oil & Grease Phenols Phosphorus Selenium Silver Sulfate Sulfide Sulfite Surfactants Thallium Tin Titanium Total Organic Nitrogen Units Conc Mass S.U. mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day mg/L lb/day Effluent Max daily 30 day max Conc Mass Conc Mass 7.58-8.83 0.11 0.16 < 0.0002 < 0.0003 0.071 0.1 0.075 0.11 < 0.001 < 0.0015 0.39 0.566 0.39 0.285 < 0.5 < 0.73 < 0.001 < 0.0015 - Intake Long term avg Conc Mass 0.29 1836 < 0.002 < 13 < 0.005 < 32 0.053 336 < 0.001 < 6.3 0.14 886 < 0.5 < 3166 < 0.001 < 6.3 mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L ng/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L mg/L lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day lb/day < 0.01 < 0.002 < 0.001 < 0.002 < 0.001 < 1.0 2.2 < 0.001 12 2.2 4.45 0.0093 < 0.002 0.266 < 4.8 < 0.04 0.49 < 0.005 < 0.001 52 < 1.0 < 0.5 < 0.03 < 0.002 < 0.01 < 0.01 < 0.015 < 0.0029 < 0.0015 < 0.0029 < 0.0015 < 1.5 3.195 < 0.0015 17.428 3.195 0.000006 0.014 < 0.0029 0.386 < 7.0 < 0.58 0.71 < 0.0073 < 0.0015 76 < 1.5 < 0.7 < 0.0436 < 0.0029 < 0.015 < 0.015 4.45 - 0.000003 - < 0.01 < 0.002 < 0.001 < 0.002 < 0.001 < 1.0 0.48 < 0.001 14 0.042 4.85 0.0061 < 0.002 0.595 < 5.1 < 0.04 < 0.1 < 0.005 < 0.001 100 < 1.0 < 0.5 < 0.03 < 0.002 < 0.01 < 0.01 < 63 < 13 < 6.3 < 13 < 6.3 < 6331 3039 < 6.3 88638 266 0.0307 39 < 13 3767 < 32390 < 253 < 633 < 32 < 6.3 633130 < 6331 < 3166 < 190 < 13 < 63 < 63 mg/L lb/day < 3.0 < 4.4 - - < 3.0 < 18994 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -28- Table 1. Effluent Characterization Using NPDES Application Form 2C Parameter Zinc Units Conc Mass mg/L lb/day Effluent Max daily 30 day max Conc Mass Conc Mass 0.087 0.13 - Intake Long term avg Conc Mass < 0.001 < 6.3 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -29- Table 2. Effluent Characterization Using Ohio EPA Data Parameter Aluminum Ammonia Arsenic Barium Cadmium Calcium Units mg/L mg/L µg/L µg/L µg/L mg/L Outfall 002 AA (200) 0.054 AA (2) 90 AA (0.2) 129 Outfall 003 506 0.066 AA (10) 174 1.75 76 Carbonaceous Biochemical Oxygen Demand (5 day) Chloride Chromium Copper Cyanide, Free Iron Lead Magnesium Manganese Mercury Nickel Nitrate+Nitrite Oil & Grease Phenolics Phosphorus Selenium Strontium mg/L mg/L µg/L µg/L mg/L mg/L µg/L µg/L µg/L µg/L µg/L mg/L mg/L mg/L mg/L µg/L µg/L AA (2) 40.3 AA (2) 2.1 AA (5) 1010 AA (2) 27 528 AA (0.2) 11.4 0.34 NA AA (10) 0.039 2.5 712 AA (2) 23.2 15.3 3.9 AA (5) 307 AA (2) 12 32 AA (0.2) 11.1 0.78 AA (2.1) AA (10) 0.035 AA (10) 447 Total Filterable Residue (Dissolved Solids) Total Kjeldahl Nitrogen Total Suspended Solids Zinc mg/L mg/L mg/L µg/L 638 0.43 6 23 362 AA (0.2) 10 22 AA = non-detection (method detection limit) Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -30- Table 3. Effluent Characterization Using Self-Monitoring Data Current Permit Limits 95th Data Range 855 76.5 95.7 43.2-102 1796 3020 4770 0-5770 1796 59 1781 645 7.66 373 1020 7.96 683 0-1260 6.8-8.1 0-718 108 0 0 0-0 Season Units Annual °F Thermal Discharge Station Operating Output pH Flow Rate Chlorine, Total Residual Annual Million BTU/Hr Annual Annual Annual Megawatts S.U. MGD Annual mg/L Annual Minutes Monitor 1795 0 720 0-1080 Annual S.U. 6.0 - 9.0 59 7.69 8.27 6.57-8.5 Annual Annual Annual Annual Annual Annual Annual Annual mg/L mg/L µg/L µg/L µg/L µg/L MGD ng/L Monitor Monitor Monitor Monitor Monitor Monitor 68 60 15 15 18 45 1796 10 12 0 563 1170 98.5 2.85 1.48 2.53 30.7 0 1510 3650 135 10.8 4.82 56.2 5-37 0-10.4 183-1680 470-4010 67.8-157 0-17.5 0-7.48 0.93-96.5 Annual S.U. 6.0 - 9.0 59 7.55 8.88 6.2-8.96 Annual Annual Annual Annual Annual mg/L mg/L µg/L MGD ng/L Monitor Monitor Monitor 70 59 18 1796 9 13.1 0 3.53 12 2.8 38.3 0 20 12 3.76 0-78.8 0-7.4 0-30.9 1.79-12 1.4-3.9 Annual Annual Units S.U. Monitor 6.0 - 9.0 1243 59 0 7.21 0 7.55 0-3 6.35-7.78 Annual mg/L 64 12 28 0-44 Outfall 002 pH Total Suspended Solids Oil and Grease Iron Boron Barium Copper Flow Rate Mercury Outfall 003 pH Total Suspended Solids Oil and Grease Copper Flow Rate Mercury Outfall 005 Color, Severity pH Total Suspended Solids Daily 50th Parameter Outfall 001 Water Temperature Chlorination/ Bromination Duration 30 day Percentiles # Obs. Monitor - 5880 Monitor 6.0 - 9.0 Monitor - 0.038 30 15 100 20 30 15 30 100 20 45 Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -31- Table 3. Effluent Characterization Using Self-Monitoring Data Current Permit Limits Parameter Zinc Copper Odor, Severity Turbidity, Severity Fecal Coliform 30 day Daily Monitor Monitor Monitor Monitor 200 400 1000 2000 Monitor Percentiles # Obs. 51 51 423 422 59 50th 88.3 20 0 1 1 95th 194 48.1 0 1 11 Data Range 16-262 2-72.9 0-1 0-3 1-100 1788 0.002 0.011 0.001-0.02 Flow Rate Season Annual Annual Annual Annual Annual Summer Winter Annual Units µg/L µg/L Units Units #/100 mL #/100 mL #/100 mL MGD Carbonaceous Biochemical Oxygen Demand (5 day) Summer mg/L 25 40 29 2.1 5.2 1-5.8 Carbonaceous Biochemical Oxygen Demand (5 day) Winter mg/L 25 40 30 3.25 11.4 1-12.6 Outfall 009 pH Oil and Grease Zinc Flow Rate Annual Annual Annual Annual S.U. mg/L µg/L MGD 20 430 Monitor 53 53 17 427 7.47 0 96.7 0.002 7.63 5.77 296 0.0461 7.1-8.47 0-8 17.7-879 0.001-0.407 Annual S.U. 6.0 - 9.0 44 6.68 6.9 6.4-7.1 6.0 - 9.0 15 - Outfall 012 pH Total Filterable Residue (Dissolved Solids) Total Suspended Solids Oil and Grease Strontium Zinc Copper Flow Rate Mercury Annual mg/L 1500 - 34 1090 1350 8.55-1470 Annual Annual Annual Annual Annual Annual Annual mg/L mg/L µg/L µg/L µg/L MGD ng/L 30 15 100 20 Monitor Monitor 48 44 9 13 15 831 8 0 0 1170 85.4 2.81 0.001 0 10.7 6.03 1580 110 36.1 0.001 0.656 0-15 0-6.7 878-1710 33-113 0-68.6 0.001-0.015 0-0.675 Outfall 023 pH Flow Rate Annual Annual S.U. MGD 6.0 - 9.0 Monitor 59 1763 7.44 0.204 7.67 0.256 7.05-7.83 0-0.329 Monitor Monitor 15 24 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -32- Table 3. Effluent Characterization Using Self-Monitoring Data Current Permit Limits Parameter Outfall 025 Total Precipitation pH Total Suspended Solids Boron Flow Rate Mercury Season Units 30 day Annual Annual Inches S.U. Monitor 6.0 - 9.0 Annual Annual Annual Annual mg/L µg/L MGD ng/L 30 Outfall 611 Total Suspended Solids Oil and Grease Flow Rate Annual Annual Annual mg/L mg/L MGD 30 15 Outfall 612 Copper, Total Iron, Total Flow Rate Annual Annual Annual µg/L µg/L MGD Outfall 631 Flow Rate Annual MGD 50th 95th Data Range 1582 101 0 8.06 0.739 8.67 0-2.76 7.5-8.87 100 114 12 115 6 7.8 171 0.005 1.9 39.7 323 0.29 4.06 0-95 130-389 0.0005-4.45 0.61-4.4 100 20 20 20 1743 0 0 0.0135 0 0.4 0.118 0-0 0-8 0-0.507 2 2 61 247 314 0 277 498 0 212-281 110-519 0-0.146 1783 38.9 63.4 0-4310 Daily Monitor Monitor Monitor Monitor 1000 1000 1000 1000 Monitor Monitor Percentiles # Obs. All values are based on annual records unless otherwise indicated. * = For minimum pH, 5th percentile shown in place of 50th percentile Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -33- Table 4. Projected Effluent Quality for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 Parameter Outfall 001 Chlorine, Total Residual Units # of Obs. # of Obs. > MDL PEQ average PEQ max. mg/L 108 0 -- -- mg/L mg/L mg/L mg/L µg/L µg/L µg/L µg/L µg/L µg/L µg/L µg/L µg/L mg/L ng/L µg/L 4 68 60 4 17 9 15 20 4 14 3 4 47 18 13 1 4 68 2 4 17 5 15 20 4 9 0 1 42 0 13 1 1211 24.06 7.592 358.7 1661.1 9.29 3187.2 128.28 1351 36.8 -2.809 10.938 -8.176 63.36 1659 35.77 10.4 491.4 2846.9 12.73 5604.8 159.7 1851 50.42 -3.848 17.675 -11.2 86.8 mg/L mg/L mg/L µg/L µg/L µg/L µg/L µg/L µg/L µg/L mg/L ng/L mg/L µg/L 4 70 59 5 4 4 4 20 3 5 18 10 1 2 4 69 2 1 4 4 4 18 0 2 0 10 1 1 730.7 29.018 5.402 40.3 480.2 569.4 848.4 20.267 -29.89 -4.2476 1389 61.03 1001 43.17 7.4 55.2 657.8 780 1162 35.727 -40.94 -6.3199 1903 83.6 Outfall 002 Total Filterable Residue (Dissolved Solids) Total Suspended Solids Oil and Grease Sulfate Iron Selenium Boron Barium Strontium, Total Zinc Cadmium Lead Copper Chlorine, Total Residual Mercury Molybdenum Outfall 003 Total Filterable Residue (Dissolved Solids) Total Suspended Solids Oil and Grease Arsenic, Total Barium Molybdenum Strontium, Total Copper Vanadium Selenium, Total Chlorine, Total Residual Mercury Iron Zinc Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -34- Table 4. Projected Effluent Quality for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 Parameter Sulfate Magnesium, Total Aluminum Units mg/L µg/L mg/L # of Obs. 1 1 2 # of Obs. > MDL 1 1 2 Outfall 005 Total Suspended Solids mg/L 64 Nitrite + Nitrate mg/L 3 Cyanide, Free mg/L 36 Sulfate mg/L 4 µg/L Boron, Total 3 µg/L Zinc 52 µg/L Lead 4 µg/L Copper 52 µg/L Molybdenum 4 µg/L Dibromochloromethane 3 µg/L Chloroform 3 Chlorine, Total Residual mg/L 18 µg/L Mercury 4 Carbonaceous Biochemical Oxygen Demand (5 day) Winter mg/L 15 Summer mg/L 19 Outfall 009 Oil and Grease Sulfate Iron Zinc PEQ average 905.2 54.31 1404 PEQ max. 1240 74.4 1923 57 3 6 4 3 52 3 52 4 0 3 0 1 26.105 96.58 0.008249 193.6 451.1 178.85 2.847 39.982 33.4 -106.2 -55.04 39.763 132.3 0.013601 265.2 618 274.37 3.9 60.132 45.76 -145.5 -75.4 15 19 8.2559 3.7393 14.001 5.6464 mg/L mg/L µg/L µg/L 53 3 3 16 5 3 3 16 4.7915 221.7 2155 164.3 7.2057 303.8 2952 225 mg/L mg/L mg/L mg/L µg/L µg/L µg/L µg/L 31 48 44 1 2 2 2 11 31 10 5 1 0 2 2 11 1299.2 8.7028 5.2348 2976 -117.9 19.31 1653.3 1494.4 14.04 6.6397 4077 -161.5 26.45 2103.2 Outfall 012 Total Filterable Residue (Dissolved Solids) Total Suspended Solids Oil and Grease Sulfate Arsenic, Total Barium Molybdenum Strontium, Total Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -35- Table 4. Projected Effluent Quality for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 Parameter Zinc Copper Vanadium Selenium, Total Chlorine, Total Residual Mercury Units µg/L µg/L µg/L µg/L mg/L ng/L # of Obs. 13 15 2 2 14 8 # of Obs. > MDL 13 11 0 0 0 2 PEQ average 132.5 75.07 ---0.9362 PEQ max. 181.4 102.8 ---1.283 Outfall 023 Sulfate Boron, Total Lead Antimony mg/L µg/L µg/L µg/L 4 4 3 3 4 4 0 0 303.7 3511 --- 416 4810 --- Outfall 025 Total Suspended Solids Arsenic Barium Boron Iron Manganese Mercury Molybdenum Phosphorus Zinc mg/L µg/L µg/L µg/L µg/L µg/L ng/L µg/L mg/L µg/L 114 1 1 13 1 1 6 1 1 1 90 1 1 13 1 1 6 1 1 1 32.48 321.35 339.45 333.71 9.96 9.96 6.75 42.09 2.22 393.8 48.98 440.2 465 496.04 13.64 13.64 9.24 57.66 3.038 539.4 MDL = method detection limit PEQ = projected effluent quality Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -36- Table 5. Ohio EPA Bioassay Acute Toxicity Results 11/14/2011 Outfall 002 003 Pimephales promelas Day 1 Day 2 Mixing grab grab Zone 0 0 0 0 0 0 Day 1 grab 0 0 Ceriodaphnia dubia Day 2 Mixing grab Zone 5 0 0 0 Values shown are percent mortality in 100% effluent Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -37- Table 6. Water Quality Criteria in the Study Area Parameter Aluminum Antimony Arsenic Barium Boron Cadmium Chlorine, Total Residual Chloroform (Trichloromethane) Copper Cyanide, Free Dibromochloromethane Dissolved solids (average) Iron Lead Magnesium Mercury Molybdenum Nitrate + Nitrite Selenium Strontium Sulfates Vanadium Zinc Units µg/L µg/L µg/L µg/L µg/L µg/L mg/L µg/L µg/L mg/L µg/L mg/L µg/L µg/L mg/L ng/L µg/L mg/L µg/L µg/L mg/L µg/L µg/L Outside Mixing Zone Criteria Average Maximum Human Agri- Aquatic Aquatic Health culture Life Life ----14 -190 900 50 100 150 340 --220 2000 --3900 33000 -50 3 6.1 --0.011 0.019 57c -140 1300 1300 500 12 18 0.7 -0.0052 0.022 4.1c -----1500 --5000 ---100 9.1 170 ----12 10000 910 1700 --20000 190000 10 100 --170 50 5 ---21000 40000 250 -----44 150 9100 25000 150 150 Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -38- Inside Mixing Zone Maximum -1800 680 4000 65000 24 0.038 2600 51 0.044 ---550 -3400 370000 --81000 -300 500 Table 7. Instream Conditions and Discharger Flow Parameter Units Stream Flows - Ohio River 1Q10 cfs 7Q10 cfs Harmonic Mean cfs Mixing Assumption % % Season Value Basis annual annual annual 10600 10600 42100 ORSANCO - Greenup to Meldahl ORSANCO - Greenup to Meldahl ORSANCO - Greenup to Meldahl average maximum 10 1 WLAs for non-carcinogens are developed using 100 percent of the 7Q10. Stream Flows - Unnamed Tributary (UT) to Pond Run 1Q10 cfs annual 0 7Q10 cfs annual 0 Harmonic Mean cfs annual 0 Mixing Assumption Hardness - Ohio River Hardness - UT Pond Run % % average maximum 100 100 mg/l mg/l annual annual 131 180 Duke Energy Beckjord Flow Rates Outfall 023 cfs Outfall 005 Outfall 002 Outfall 012 Outfall 003 Outfall 025 Outfall 009 annual    0.396 0.0031 6.62 0.0015 18.6 0.296 0.107 WLAs for non-carcinogens are developed using 100 percent of the 7Q10. ORSANCO - Greenup to Meldahl BWQR - Southwest Ohio River Tributaries    95th percentile monthly averages Form 2C maximum 30 day average 95th percentile of monthly averages Form 2C maximum 30 day average Form 2C maximum 30 day average Form 2C maximum 30 day average Form 2C maximum 30 day average Background Water Quality - Ohio River 293 0 ORSANCO; 2006-2011; n=30; 0= 50 percent, but < 100 percent of the maximum PEL or PEQavg >= 50 percent, but < 100 percent of the average PEL. Monitoring is appropriate. Mercury Group 5: Maximum PEQ >= 100 percent of the maximum PEL or average PEQ >= 100 percent of the average PEL, or either the average or maximum PEQ is between 75 and 100 percent of the PEL and certain conditions that increase the risk to the environment are present. Limit recommended. Limits to Protect Numeric Water Quality Criteria Parameter Copper Recommended Effluent Limits Period Average Maximum -64 Units µg/L Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -43-          Table 9. Parameter Assessment for Outfalls 002, 003, 005, 009, 012, 023, and 025 Outfall 003 Group 1: Due to a lack of criteria, the following parameters could not be evaluated at this time. Aluminum Group 2: PEQ < 25 percent of WQS or all data below minimum detection limit. WLA not required. No limit recommended; monitoring optional. Chlorine, Total Residual Vanadium Group 3: Molybdenum Strontium PEQmax < 50 percent of maximum PEL and PEQavg < 50 percent of average PEL. No limit recommended; monitoring optional. Arsenic Mercury Iron Group 4: Magnesium Barium Dissolved solids (average) Sulfates Selenium Zinc    PEQmax >= 50 percent, but < 100 percent of the maximum PEL or PEQavg >= 50 percent, but < 100 percent of the average PEL. Monitoring is appropriate. Copper Group 5: Maximum PEQ >= 100 percent of the maximum PEL or average PEQ >= 100 percent of the average PEL, or either the average or maximum PEQ is between 75 and 100 percent of the PEL and certain conditions that increase the risk to the environment are present. Limit recommended. No parameters meet these criteria. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -44- Table 9. Parameter Assessment for Outfalls 002, 003, 005, 009, 012, 023, and 025 Outfall 005 Group 1: Due to a lack of criteria, the following parameters could not be evaluated at this time. No parameters meet this criterion. Group 2: PEQ < 25 percent of WQS or all data below minimum detection limit. WLA not required. No limit recommended; monitoring optional. Dibromochloromethane Molybdenum Group 3: Chlorine, Total Residual Boron PEQmax < 50 percent of maximum PEL and PEQavg < 50 percent of average PEL. No limit recommended; monitoring optional. Chloroform (Trichloromethane) Nitrate + Nitrite Group 4: Cyanide, Free Sulfates Lead PEQmax >= 50 percent, but < 100 percent of the maximum PEL or PEQavg >= 50 percent, but < 100 percent of the average PEL. Monitoring is appropriate. Zinc Group 5: Maximum PEQ >= 100 percent of the maximum PEL or average PEQ >= 100 percent of the average PEL, or either the average or maximum PEQ is between 75 and 100 percent of the PEL and certain conditions that increase the risk to the environment are present. Limit recommended. Limits to Protect Numeric Water Quality Criteria Parameter Copper Mercury Recommended Effluent Limits Period Average Maximum -51 12 1700 Units µg/L ng/L                               Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -45- Table 9. Parameter Assessment for Outfalls 002, 003, 005, 009, 012, 023, and 025 Outfall 009 Group 1: Due to a lack of criteria, the following parameters could not be evaluated at this time. No parameters meet this criterion. Group 2: PEQ < 25 percent of WQS or all data below minimum detection limit. WLA not required. No limit recommended; monitoring optional. No parameters meet these criteria. Group 3: PEQmax < 50 percent of maximum PEL and PEQavg < 50 percent of average PEL. No limit recommended; monitoring optional. Iron Group 4: Sulfates Zinc PEQmax >= 50 percent, but < 100 percent of the maximum PEL or PEQavg >= 50 percent, but < 100 percent of the average PEL. Monitoring is appropriate. No parameters meet these criteria. Group 5: Maximum PEQ >= 100 percent of the maximum PEL or average PEQ >= 100 percent of the average PEL, or either the average or maximum PEQ is between 75 and 100 percent of the PEL and certain conditions that increase the risk to the environment are present. Limit recommended. No parameters meet these criteria. Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -46- Table 9. Parameter Assessment for Outfalls 002, 003, 005, 009, 012, 023, and 025 Outfall 012 Group 1: Due to a lack of criteria, the following parameters could not be evaluated at this time. No parameters meet this criterion. Group 2: PEQ < 25 percent of WQS or all data below minimum detection limit. WLA not required. No limit recommended; monitoring optional. Arsenic Chlorine, Total Residual Group 3: Vanadium PEQmax < 50 percent of maximum PEL and PEQavg < 50 percent of average PEL. No limit recommended; monitoring optional. Barium Zinc Group 4: Molybdenum Strontium    Dissolved solids (average) Sulfates PEQmax >= 50 percent, but < 100 percent of the maximum PEL or PEQavg >= 50 percent, but < 100 percent of the average PEL. Monitoring is appropriate. Mercury Group 5: Maximum PEQ >= 100 percent of the maximum PEL or average PEQ >= 100 percent of the average PEL, or either the average or maximum PEQ is between 75 and 100 percent of the PEL and certain conditions that increase the risk to the environment are present. Limit recommended. Limits to Protect Numeric Water Quality Criteria Parameter Copper Recommended Effluent Limits Period Average Maximum -64 Units µg/L       Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -47- Table 9. Parameter Assessment for Outfalls 002, 003, 005, 009, 012, 023, and 025 Outfall 023 Group 1: Due to a lack of criteria, the following parameters could not be evaluated at this time. No parameters meet this criterion. Group 2: PEQ < 25 percent of WQS or all data below minimum detection limit. WLA not required. No limit recommended; monitoring optional. Antimony Group 3: PEQmax < 50 percent of maximum PEL and PEQavg < 50 percent of average PEL. No limit recommended; monitoring optional. Boron Group 4: Zinc Sulfates PEQmax >= 50 percent, but < 100 percent of the maximum PEL or PEQavg >= 50 percent, but < 100 percent of the average PEL. Monitoring is appropriate. No parameters meet these criteria. Group 5:                                Maximum PEQ >= 100 percent of the maximum PEL or average PEQ >= 100 percent of the average PEL, or either the average or maximum PEQ is between 75 and 100 percent of the PEL and certain conditions that increase the risk to the environment are present. Limit recommended. No parameters meet these criteria.                                                                                                                                                                                                                                                         Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -48- Table 9. Parameter Assessment for Outfalls 002, 003, 005, 009, 012, 023, and 025 Outfall 025 Group 1: Due to a lack of criteria, the following parameters could not be evaluated at this time. Manganese Group 2: Phosphorus PEQ < 25 percent of WQS or all data below minimum detection limit. WLA not required. No limit recommended; monitoring optional. Boron Group 3: Iron Molybdenum PEQmax < 50 percent of maximum PEL and PEQavg < 50 percent of average PEL. No limit recommended; monitoring optional. No parameters meet these criteria. Group 4: PEQmax >= 50 percent, but < 100 percent of the maximum PEL or PEQavg >= 50 percent, but < 100 percent of the average PEL. Monitoring is appropriate. Mercury Group 5: Maximum PEQ >= 100 percent of the maximum PEL or average PEQ >= 100 percent of the average PEL, or either the average or maximum PEQ is between 75 and 100 percent of the PEL and certain conditions that increase the risk to the environment are present. Limit recommended. Limits to Protect Numeric Water Quality Criteria                Parameter Arsenic Barium Zinc Recommended Effluent Limits Period Average Maximum 100 340 220 2000 200 200 Units µg/L µg/L µg/L                PEL = preliminary effluent limit PEQ = projected effluent quality WLA = wasteload allocation WQS = water quality standard Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -49- Table 10. Final Effluent Limits for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 Concentration 30 Day Daily Loading (kg/day)a 30 Day Daily Average Maximum Average Maximum Basisb Parameter Outfall 001 Units Water Temperature Station Operating Output pH °F MW S.U. - - - - - - - - - - - - - Monitor - - - - - - - - - - - 5880 6.0 - 9.0 - EP/Mc 316(a) Demo EP/WQS Flow Rate Chlorine, Total Residual MGD mg/L - - - - - - - - - - - - - Monitor - - - - - - - - - - - 0.038 - EP/Mc WQS Chlorination/Bromination Duration Minutes - - - - - - - - - - - - - Monitor - - - - - - - - - - - - EP MGD S.U. mg/L mg/L µg/L µg/L mg/L ng/L µg/L - - - - - - - - - - - - - Monitor - - - - - - - - - - - 6.0 - 9.0 30 99.6 231 769 15 20 116 154 - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - 64 0.494 EP/Mc EP/WQS FEG FEG EP EP EP RP WLA MGD S.U. mg/L mg/L ng/L µg/L - - - - - - - - - - - - - Monitor - - - - - - - - - - - 6.0 - 9.0 30 100 1363 4552 15 20 681 908 - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - - EP/Mc EP/WQS FEG/ABS FEG/ABS EP RP Flow Rate pH MGD S.U. - - - - - - - - - - - - - Monitor - - - - - - - - - - - 6.0 - 9.0 - EP/Mc EP/WQS Total Suspended Solids mg/L 30 EP/PD Outfall 002 Flow Rate pH Total Suspended Solids Oil & Grease Barium Boron Iron Mercury Copper Outfall 003 Flow Rate pH Total Suspended Solids Oil & Grease Mercury Copper Outfall 005 45 2.27 3.41 Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -50- Table 10. Final Effluent Limits for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 Parameter Units Carbonaceous Biochemical Oxygen Demand (5 day) Turbidity Severity mg/L Units E. coli - Summer Fecal Coliform - Winter Zinc Mercury Copper #/100 mL Concentration 30 Day Daily Loading (kg/day)a 30 Day Daily Average Maximum Average Maximum 1.89 3.03d 25 40d - - - - - - - - - - - - - Monitor - - - - - - - - - - - 130 292d -- -- d Basisb EP/PD EP WQS #/100 mL µg/L ng/L µg/L 1000 2000 --- - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - 51 ? WQS RP WLA WLA MGD S.U. mg/L µg/L - - - - - - - - - - - - - Monitor - - - - - - - - - - - 6.0 - 9.0 15 20 - - - - - - - - - - - - - Monitor - - - - - - - - - - - - EP/Mc EP/WQS FEG EP MGD S.U. mg/L mg/L µg/L mg/L ng/L µg/L - - - - - - - - - - - - - Monitor - - - - - - - - - - - 6.0 - 9.0 30 100 15 20 - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - 15 24 - EP/Mc EP/WQS FEG FEG EP EP RP WLA/ABS MGD S.U. - - - - - - - - - - - - - Monitor - - - - - - - - - - - 6.0 - 9.0 - EP/Mc EP/WQS Total Precipitation Inches - - - - - - - - - - - - - Monitor - - - - - - - - - - - - EP/Mc Flow Rate MGD - - - - - - - - - - - - - Monitor - - - - - - - - - - - - EP/Mc Outfall 009 Flow Rate pH Oil & Grease Zinc Outfall 012 Flow Rate pH Total Suspended Solids Oil & Grease Zinc Total Filterable Residue Mercury Copper Outfall 023 Flow Rate pH Outfall 025 Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -51- Table 10. Final Effluent Limits for Outfalls 001, 002, 003, 005, 009, 012, 023, and 025 Concentration 30 Day Daily Parameter pH Total Suspended Solids Arsenic Barium Zinc Mercury Units S.U. mg/L µg/L µg/L µg/L ng/L Loading (kg/day)a 30 Day Daily Average Maximum Average Maximum 6.0 - 9.0 30 100 - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - - - - - - - - - - - - - - Monitor - - - - - - - - - - - - Basisb EP/WQS BPJ WLA WLA WLA RP a Effluent loadings based on average design discharge flow of: Outfall 002 – 2.041 MGD Outfall 003 – 12 MGD (actual average design flow is 18.78 MGD but 12 MGD is used due to ABS rules) Outfall 005 – 0.02 MGD Outfall 012 – 0.001 MGD b Definitions: c Monitoring of flow and other indicator parameters is specified to assist in the evaluation of effluent quality and treatment plant performance. d 7 day average limit. 316(a) Demo. = Alternate thermal limitation developed under Section 316(a) of the Clean Water Act ABS = Antibacksliding Rule (OAC 3745-33-05(E) and 40 CFR Part 122.44(l)) BEJ = Best Engineering Judgment BPJ = Best Professional Judgment EP = Existing Permit FEG = Federal Effluent Guidelines, 40 CFR Part 423, Steam Electric Power Generating Point Source Category M = BEJ of Permit Guidance 2: Determination of Sampling Frequency Formula for Industrial Waste Discharges RP = Reasonable Potential for requiring water quality-based effluent limits and monitoring requirements in NPDES permits (3745-33-07(A)) PD = Plant Design WLA = Wasteload Allocation procedures (OAC 3745-2) WQS = Ohio Water Quality Standards (OAC 3745-1) Fact Sheet for NPDES Permit Renewal, Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -52- Attachment 1. Applicable Federal Effluent Guidelines Steam Electric Power Generating Point Source Category 40 CFR 423.12(b)(3) – Low volume wastewater Best Practicable Control Technology Available (BPT) Parameter (mg/L) Daily Maximum 30-Day Average Total Suspended Solids 100 30 Oil & Grease 20 15 40 CFR 423.12(b)(4) – Fly and bottom ash transport water Best Practicable Control Technology Available (BPT) Parameter (mg/L) Daily Maximum 30-Day Average Total Suspended Solids 100 30 Oil & Grease 20 15 40 CFR 423.13(b)(1) – Once-through cooling water Best Available Technology Economically Achievable (BAT) Parameter (mg/L) Daily Maximum 30-Day Average Total Residual Chlorine 0.2 40 CFR 423.12(b)(9) – Coal pile runoff Best Practicable Control Technology Available (BPT) Parameter (mg/L) Daily Maximum 30-Day Average Total Suspended Solids 50 - Fact Sheet for NPDES Permit Renewal, Duke Energy Ohio, Inc. – Walter C. Beckjord Station, 2013 -53-